- Suitable for multi-positional mounting, If ball check vent limiting device is installed, mount in an upright position only
- Note: capacities are used to determine the maximum multiple appliance load, the largest single appliance served by the regulator should not exceed the maximum individual load specified above
- Minimum Regulation: Suitable for pilot flow applications
- 65 psi emergency exposure limit (inlet side only)
- 1/8 in NPT vent connection
- 3 in swing radius
- Maximum Individual Load: 140000 Btu/hr
- Total load of multiple appliance combined capacity: 250000 Btu/hr
- 1 to 2 psi inlet pressure
- 7 to 11 in wc, 1.7 to 2.7 kPa at 2 psi (white CSA certified springs)
- Body MaterialAluminumEnd StyleThreadNominal Size1/2 inPressure Rating2 psiDimensions3-1/2 in HInlet to Outlet Length4.2ManufacturerMaxitrol CompanyManufacturer #325-3LSeries325Temperature Rating-40 to 205 deg F